Order No. 1-5469-42-22
Model No. LTC-1200
JAN Code 4582619704730

Features

  • Uses stainless steel coil with excellent durability.
  • New HFC refrigerant with zero ozone depletion potential is used.
  • Since the wetted part is made of stainless steel, it has excellent durability and can circulate pure water.
  • It has powerful cooling capacity and can be used in a wide range of fields.
  • An external temperature sensor can be used to directly measure the temperature of an object.
  • Has overload protection device, high-pressure switch, safety breaker and self-diagnostic function.

Spec

  • Temperature range (°C): -20 to +30
  • Temperature Adjustment Accuracy ±2.0°C(Room Temperature 20°C/Maximum Circulation Volume/Power Supply 100 VAC 50/60Hz/Setting 5~30°C/At No Load)
  • Circulation system: Closed system counter circulation
  • Type of solution used: city water, pure water, ethylene glycol, etc.
  • Circulation Pump (50/60Hz): Maximum Flow Rate 20/20L/min, Maximum Pump Head 9.5/12.9 m (Circulation Pump Performance When Only Pump Is Used)
  • Cooling Capacity: 1250 W at10°C (Value at ambient temperature of 20°C, 50 Hz, no load.)
  • Circulation Nozzle Outer Diameter: φ11 mm (Applicable Tube Inner Diameter φ9 mm)
  • Freezer: 650 W
  • Liquid Tank: φ280 x H280mm Approx. 16 L
  • Coolant: R407C
  • Power: 100 VAC 50/60Hz
  • Timer: 1 minute to 47 hours 59 minutes (1 minute increments)
  • Self-Diagnosis Function: Upper/Lower Temperature Abnormality Detection, Sensor Abnormality, Chiller Overload Relay, Chiller Protection Timer, Power Failure Detection, Control Temperature Abnormality, Memory Error
  • External Input/Output: External Temperature Sensor Input Terminal, Analog Output Terminal for Thermometer (1 ~5 VDC) Alarm Output Terminal (12 VDC ~17 VDC)
  • Size: 357 x 407 x 800 mm
  • Weight: Approx. 45 kg
  • *Pure water that can be used has a conductivity of 10 μS/cm or more (low purity).
  • This product is compatible with the validation service (IQ/OQ). Please contact us.
  • *The validation service is a service where installation qualification (IQ) and operation qualification (OQ) are performed at the customer's site and an inspection report is submitted.




Hubungi:
PT Bopana Arga Prima Jaya
Jalan Jupiter VI Perum Bintang Metropol
Blok A7 No.16 Bekasi Utara 17122
Jawa Barat, Indonesia
Telp : 021-22163350
Hp : 08119762505 / 081285345374
Email : boney@bapj.co.id / tesa@bapj.co.id

Produk Terkait

                                                                                      PT. Bopana Arga Prima Jaya

Office

Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16 Bekasi Utara 17122 , Bekasi
Bekasi , Indonesia

Contact
021 -2216 3350
info@bapj.co.id
Share
apartmentenvelopebookmarkcarttagphone-handsetearthhistorymagnifiercross
× How can I help you?