The Fluke 116 DMM provides the features you need to quickly troubleshoot HVAC equipment
The Fluke 116 was specifically designed for HVAC professionals. It has everything you need to quickly troubleshoot problems with HVAC equipment and flame sensors, including a built-in thermometer to measure temperatures up to 400°C (752°F) and microamps to test flame sensors. The Fluke 116 also measures resistance, continuity, frequency, and capacitance. And the large white LED backlight makes it easy to see results even in poorly lit areas.
Fluke 116 multimeters are independently tested for safe use in CAT III 600 V environments.
Other useful features:
Specifications | ||
Maximum voltage between any terminal and earth ground | 600 V | |
Safety | IEC 61010-1: Pollution Degree 2 IEC 61010-2-033: CAT III 600V |
|
Display | Digital: 6,000 counts, updates 4 per second | |
Bar graph | 33 segments, updates 32 per second | |
Operating temperature | -10°C to + 50°C | |
Storage temperature | -40°C to + 60°C | |
Battery type | 9 volt Alkaline, IEC 6LR61 | |
Battery life | 400 hours typical, without backlight | |
Accuracy Specifications | ||
DC millivolts | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
DC volts | Range/resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.00 V / 0.1 V |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
Auto volts | Range/resolution | 600.0 V / 0.1 V |
Accuracy | 2.0% + 3 (DC, 45 Hz to 500 Hz) 4.0% + 3 (500 Hz to 1 kHz) |
|
AC millivolts1 True RMS | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
AC volts1 True RMS | Range/resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
Continuity | Range/resolution | 600 Ω / 1 Ω |
Accuracy | Beeper on < 20 Ω, off > 250 Ω detects opens or shorts of 500 μs or longer. |
|
Ohms | Range/resolution | 600.0 Ω / 0.1 Ω 6.000 kΩ / 0.001 kΩ 60.00 kΩ / 0.01 kΩ 600.0 kΩ / 0.1 kΩ 6.000 MΩ / 0.001 MΩ |
Accuracy | 0.9% + 1 | |
Range/Resolution | 40.00 MΩ / 0.01 MΩ | |
Accuracy | 5% + 2 | |
Diode Test | Range/resolution | 2.00 V / 0.001 V |
Accuracy | 0.9% + 2 | |
Capacitance | Range/resolution | 1000 nF / 1 nF 10.00 μF / 0.01 μF 100.0 μF / 0.1 μF 9999 μF / 1 μF 100 μF to 1000 μF |
Accuracy | 1.9% + 2 | |
Range/resolution | > 1000 μF | |
Accuracy | 5% + 20% | |
Lo-Z Capacitance | Range | 1 nF to 500 μF |
Accuracy | 10% + 2 typical | |
Temperature² (Type-K thermocouple) |
Range/resolution | -40°C to 400°C / 0.1°C |
Accuracy | 1% + 10² | |
Range/resolution | -40°F to 752°F / 0.2°F | |
Accuracy | 1% + 18² | |
AC μA true-rms (45 Hz to 500 Hz) | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.5% + 3 | |
DC μamps | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.0% + 2 | |
Hz (V or A input)² | Range/resolution | 99.99 Hz / 0.01 Hz 999.9 Hz / 0.1 Hz 9.999 kHz / 0.001 Hz 50.00 kHz / 0.01 Hz |
Accuracy | 0.1% + 2 | |
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V. 2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe. 3. Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current. 4. Temperature Range/Resolution: -40°F to 752°F / 0.2°F. |
||
Mechanical and General Specifications | ||
Size | 167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in) | |
Weight | 550 g | |
Warranty | 3 years |