Working in cramped electrical boxes and trying to find a safe metallic contact points is often challenging. The Fluke T6-600 Electrical Tester with FieldSense™ technology, lets you quickly and safely take measurements by sliding the open fork over a conductor, without the need for test leads. The T6-600 works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
FieldSense™ technology is a breakthrough in how voltage is measured. Other open fork testers detect a magnetic field to show AC current. FieldSense™ technology detects an electrical field, which interacts with a reference signal created by the T6 tester, which shows the measurement value on the tester’s display.
Tips on using FieldSense technology
The electrical tester offers a variety of measurement options giving you an all-in-one troubleshooting tool. Measure true rms voltage and current from 0 to 200 A AC or 1 to 600 V AC or DC. You can also gather resistance measurement from 1 Ω to 2000 Ω. With the easy-to-read backlit display, you can keep see your work in dark environments and keep your most recent measurement on the screen with the HOLD button for easy viewing. The T6-600 also accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation.
Function | Requires test leads | Range | Resolution | Accuracy[1] |
---|---|---|---|---|
FieldSense ac voltage true-rms |
No | 600 V | 1 V | ±(3% + 3 counts) 45 Hz - 66 Hz[2] [3] |
FieldSense ac current true-rms |
No | 200.0 A | 0.1 A | ±(3% + 3 counts) 45 Hz - 66 Hz |
Volts ac true-rms | Yes | 600 V | 1 V | ±(1.5% + 2 counts) 45 Hz - 66 Hz |
Volts dc | Yes | 600 V | 1 V | ±(1% + 2 counts) |
Resistance | Yes | 2000 Ω | 1 Ω | ±(1% + 2 counts) |
Safety | 600 V CAT III | |||
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground. Accuracy[3]: FieldSense is specified from 16 V to 100 % of range. |
Calibration | 1-year calibration cycle | |
---|---|---|
Dimensions | 61.1 x 259.3 x 43.8 mm | |
Jaw opening | 17.8 mm | |
Weight | 0.35 kg (0.78 lb) | |
Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
Altitude | Operating | 2,000 m (6,562 feet) |
Storage | 10,000 m (32,808 feet) | |
Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
(< 64.4 °F or > 82.4 °F) | ||
Safety | IEC/EN 61010-1: Pollution Degree 2 | |
Electromagnetic Environment | IEC/EN 61326-1: Portable |