| AC/DC Voltage Measurement | |
| Range | 0.3 to 700V |
| Accuracy | ±(3% R + 2ct) |
| Resolution | 0.3 to 399.9V: 0.1V 400 to 700V: 1V |
| Frequency Range | DC & 15.3 to 800Hz |
| Input Impedance | 400kΩ |
| Insulation Measurement | |
| Test Voltage / Resistance Range | 250V: 50kΩ to 10GΩ 500V: 100kΩ to 20GΩ 1000V: 200kΩ to 40GΩ |
| Measurement Accuracy | 250V: ±(3% R + 2ct)+0.4%/GΩ 500V: ±(3% R + 2ct)+0.2%/GΩ 1000V: ±(3% R + 2ct)+0.1%/GΩ |
| Auto Discharge | Discharge time < 2s/µF From Vtest to 25V |
| Live Circuit Indicator | Inhibit test if terminal voltage > 25V prior to initialization of test |
| Continuity Measurement | |
| Ranges | 0.00 to 10Ω (200mA test current) |
| Accuracy | ± (2% R + 2ct) with lead compensation |
| Open Voltage | ≥ 6V |
| General Features | |
| Timer | 0:00 to 39:59mn, with 1s resolution |
| Display | Backlit digital with bargraph |
| Power Supply | Six AA batteries (NEDA 15A or IEC LR6) |
| Battery Life | ≥1500 IR tests at 1000 V into 1MΩ with a duty cycle of 5 seconds on and 1 min off. ≥3000 R tests of 1Ω with a duty cycle of 5 seconds on and 1min off. |
| Dimensions | 8.31 x 4.25 x 2.36” (211 x 108 x 60mm) |
| Weight | 1.87 lbs (850g) |
| Altitude Operating | 2000m |
| Operating Temperature | -4° to +131°F (-20° to +55°C) & 20 to 80% RH |
| Storage Temperature | -22° to +176°F (-30° to +80°C) & 10 to 90% RH, without batteries |
| IP Rating | IP 54 |
| Safety Compliance | IEC/EN 61010-1, 600V CAT IV, IEC 61557![]() |
BOPANA ARGA PRIMA JAYA
Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16, RT.004/RW.013, Perwira, Kec. Bekasi Utara, Kota Bks, Jawa Barat 17122
Phone :+62 -21-2216-3350 & +62-21- 292531-86
Whatsapp : +62 812-8202-721 & +62 811-1871-501
Email : info@bapj.co.id || bopana.argaprima@gmail.com