VT/PT Ratio Range | Auto-Ranging: 0.8000:1 to 8000.0:1 |
VT/PT Accuracy | 0.8000 to 9.9999: ±0.2% of Reading 10.000 to 999.99: ±0.1% of Reading 1000.0 to 4999.9: ±0.2% of Reading 5000.0 to 8000.0: ±0.25% of Reading |
CT Ratio Range | Auto-Ranging: 0.8000 to 1000.0 |
CT Accuracy | ±0.5% of Reading |
Excitation Signal | VT/PT Mode: 32Vrms max CT Mode: Auto Level 0 to 1A, 0.1 to 4.5Vrms |
Excitation Current Display | Range: 0 to 1000mA Accuracy: ±(2% of Reading +2mA) |
Excitation Frequency | 70Hz |
Display | LCD 16 character, 2 line, large format, LED backlight, day/night visible |
Languages Supported | English, Spanish, French, Italian, German, Portuguese |
Communication | Optically isolated USB 2.0 |
Data Storage | Up to 10,000 complete measurements |
Power Source | Two rechargeable 12V NiMH batteries (included) |
Battery Life | Up to 10 hours of continuous operation |
Low Battery Indication | LED and LCD |
External Charger | 90 to 240V, 50/60Hz (smart charger) |
Charging Time | <4 hours |
Measurement Method | In accordance with ANSI/IEEE Std. C57.12.90-2006 |
Software | DataView analysis software included |
Dimensions | 10.70 x 9.76 x 5.12” (272 x 248 x 130mm) |
Weight | 8.1 lbs (3.7kg) |
Operation Temperature | 14° to 122°F (-10° to 50°C) |
Storage Temperature | -4° to 140°F (-20° to 60°C) |
Index of Protection | IP40 (lid open), IP53 (lid closed) |
Double Insulated | Yes |
CE Approved | Yes |
Safety Compliance | IEC 61010-1 (1995-A2) 50V CAT IV Pollution 2 |