AC Current Probe Model SR759
The SR759 probe is a range selectable probe that offers four switch selectable ranges: 1, 10, 100 or 1000A. This probe has a voltage output proportional to the current measured in the jaw of the probe. The SR759 has an integral 5 ft (1.5m) lead terminated by shrouded banana plugs compatible with DMMs and other instruments. The high accuracy, high sensitivity and low phase shift makes this probe an excellent choice for use in a wide range of power quality applications, including very low or leakage current measurements.
Specifications :
Maximum Conductor Size |
2.05" (52mm) |
Current Range |
1A, 10A, 100A, 1000Arms AC |
Measurement Range |
1mA to 1.2A, 0.01 to 12A, 0.1 to 120A, 1 to 1200A |
Output |
5 ft (1.5m) lead with safety 4mm banana plug |
Transformation Ratio |
1:1, 10:1, 100:1, 1000:1 |
Output Signal |
1000mV/AAC (1V @ 1A), 100mV/AAC (1V @ 10A), 10mV/AAC (1V @ 100A), 1 mV/AAC (1V @ 1000A) |
Accuracy 50/60Hz |
0.7% ± 1mV @ 1A, 0.5% @ 10A, 0.2% @100A, 0.2% @ 1000A |
Frequency Range |
30Hz to 3kHz with current derating |
Phase Shift at 50Hz |
1° @ 1000A |
Open Secondary Voltage |
8V peak |
Load Impedance |
10MΩ, 100kΩ min with derating |
Overload |
1200A for 40 mn ON then 20 mn OFF |
Dimensions (H x W x D) |
4.37 x 8.50 x 1.77” (111 x 216 x 45mm) |
Weight |
1.21 lbs (550g) |
Operating Temperature |
14° to +122°F (-10° to +50°C) |
Storage Temperature |
-4° to +158°F (-20° to +70°C) |
Operating Humidity |
90% RH |
Pollution Degree |
2 |
Ingress Protection (Ip) |
IP40 |
EMC |
EN 61326-1 |
Safety Compliance |
EN/IEC 61010-1 600V CAT III, EN/IEC 61010-032 |