AC/DC Voltage Measurement | |
Range | 1 to 4000V |
Accuracy | 1 to 99.9V: ±(1% R + 5ct) 100 to 4000V: ±(1% R + 3ct) |
Resolution | 1 to 99.9V: 0.1V 100 to 999V: 1V 1000 to 4000V: 2V |
Frequency Range | 1 to 2500V: DC or 15 to 500Hz 2501 to 4000V: DC |
Input Impedance | 750kΩ or 3MΩ (range dependent) |
Insulation Measurement | |
Test Voltage / Resistance Range | 500V: 30kΩ to 2TΩ 1000V: 100kΩ to 4TΩ 2500V: 100kΩ to 10TΩ 5000V: 300kΩ to 10TΩ |
Measurement Accuracy | 30kΩ to 39.99GΩ: ±(5% R + 3ct) 40.0GΩ 10TΩ: ±(15% R + 10ct) |
Variable Voltage | 40 to 5,100V |
Auto Discharge | Discharge time < 7s/µF from Vtest to 25V @ 5000V |
Live Circuit Indicator | Test inhibition if terminal voltage > 3, 10, 20% (selectable by user) of test voltage |
General Features | |
Programmable Alarm | Yes |
DAR – PI – DD – R(t) | Yes |
Ramp Mode | No |
Step Mode | No |
Capacitance Measurement | 0.005 to 49.99µf |
Leakage Current Measurement | 0 to 3mA |
Open Circuit Voltage | ≤ 1.1 x Vn ±2V (Vn ±2% in variable mode) |
Memory | 128kB Memory / Stores over 1500 test results |
Communication | Serial port RS-232 with USB adapter |
Software | DataView Software (included) |
Power Supply | Rechargeable NIMH battery pack; external 85-256V, 50/60Hz |
Battery Life | ≥ 1500 tests at 5000V into 5MΩ with a duty cycle of 5 seconds on and 25 seconds off |
Charging Time | 6 hours approximately (charging allowed during tests) |
Dimensions | 10.63 x 9.84 x 7.09” (270 x 250 x 180mm) |
Weight | 9.5 lbs (4.3kg) |
Altitude Operating | 2000m |
Operating Temperature | 14° to +131°F (-10° to +55°C) ≤80% RH |
Storage Temperature | -40° to +158°F (-40° to +70°C) ≤90% RH |
IP Rating | IP 53 |
Safety Compliance | EN 61010-1, EN 61557, 1000V CAT III, Pollution Degree 2, CE |
BOPANA ARGA PRIMA JAYA
Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16, RT.004/RW.013, Perwira, Kec. Bekasi Utara, Kota Bks, Jawa Barat 17122
Phone :+62 -21-2216-3350 & +62-21- 292531-86
Whatsapp : +62 812-8202-721 & +62 811-1871-501
Email : info@bapj.co.id || bopana.argaprima@gmail.com