AC/DC Voltage Measurement | |
Range | 0.3 to 700V |
Accuracy | ±(3% R + 2ct) |
Resolution | 1 to 99.9V: 0.1V 100 to 999V: 1V 1000 to 4000V: 2V |
Frequency Range | DC & 15.3 to 800Hz |
Input Impedance | 400kΩ |
Insulation Measurement | |
Test Voltage / Resistance Range | Test Voltage: Variable 10 to 100V (1V steps) 10V: 2kΩ to 2GΩ 25V: (Vtest/5)kΩ to (Vtest/5) GΩ 100V: 20kΩ to 20GΩ |
Measurement Accuracy | 2-999kΩ only: ±(4% + 20 ct) All other ranges: ±(3% + 2 ct)+(10%V) per 100MΩ |
Auto Discharge | Discharge time < 2s/µF From Vtest to 25V |
Live Circuit Indicator | Inhibit test if terminal voltage > 25V prior to initialization of test |
Continuity Measurement | |
Ranges | 0.00 to 10Ω (200mA test current) 0.0 to 100Ω (20mA test current) |
Accuracy | ± (2% R + 2ct) with lead compensation |
Open Voltage | ≥ 6V |
Resistance Measurement | |
Range | 1Ω to 1000kΩ |
Accuracy | ± (3% R + 2ct) |
Open Voltage | Approximately 4.5V |
General Features | |
Programmable Alarm | Yes |
Timer | 0:00 to 39:59mn, with 1s resolution |
Display | Backlit digital with bargraph |
Power Supply | Six AA batteries (NEDA 15A or IEC LR6) |
Battery Life | ≥ 6000 IR tests at 100V into 100kΩ with a duty cycle of 5 seconds on and 1 min off. ≥ 3000 R tests of 1Ω with a duty cycle of 5 seconds on and 1min off. |
Dimensions | 8.31 x 4.25 x 2.36” (211 x 108 x 60mm) |
Weight | 1.87 lb (850g) |
Altitude Operating | 2000m |
Operating Temperature | -4° to +131°F (-20° to +55°C) & 20 to 80% RH |
Storage Temperature | -22° to +176°F (-30° to +80°C) & 10 to 90% RH, without batteries |
IP Rating | IP 54 |
Safety Compliance | IEC/EN 61010-1, 600V CAT IV, IEC 61557 |
BOPANA ARGA PRIMA JAYA
Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16, RT.004/RW.013, Perwira, Kec. Bekasi Utara, Kota Bks, Jawa Barat 17122
Phone :+62 -21-2216-3350 & +62-21- 292531-86
Whatsapp : +62 812-8202-721 & +62 811-1871-501
Email : info@bapj.co.id || bopana.argaprima@gmail.com