Inputs | 4 Voltage / 4 Current | ||||
Sample Rate | 256 per Cycle | 12.8kHz at 50Hz | 15.36kHz at 60Hz | ||
Specification | Range | Measurement Range | Resolution | Accuracy (Typical) | |
Volt | |||||
Vrms (AC + DC) | 1000V P to N 2000V P to P |
2 to 1000V | 0.1V | ±0.5% Rdg + 200mV | |
Vpk | 1414V | 2 to 1000V | 0.1V | ±3% Rdg + 2V | |
Vrms Half Cycle | 1000V P to N 2000V P to P |
2 to 1000V | 0.1V | ±0.8% Rdg + 1V | |
Amps (accuracy excluding clamp accuracy) | |||||
Amps (AC + DC) | SR193 & MR193 MN193 5A MN193 100A |
1 to 1000A 5mA to 5A 100mA to 100A |
0.1A 1mA 10mA |
±0.5% Rdg + 200mA ±0.5% Rdg + 2mA ±0.5% Rdg + 20mA |
|
AmpFlex& MiniFlex | Range 100A Range 6500A Range 10kA |
100mA to 100A 10 to 6500A 10A to 10kA |
10mA 0.1A & 1A 1A |
±0.5% Rdg + 30mA ±0.5% Rdg + 3A ±0.5% Rdg + 3A |
|
Apk | SR193 & MR193 MN193 5A MN193 100A |
1 to 1414A 5mA to 7.017A 100mA to 141.4A |
0.1A 1mA 10mA |
±1% Rdg + 2A ±1% Rdg + 20mA ±1% Rdg + 200mA |
|
Apk AmpFlex & MiniFlex |
Range 100A Range 6500A Range 10kA |
100mA to 100A 10 to 6500A 10A to 10kA |
1A 0.1A & 1A 1A |
±3% Rdg + 600mA ±3% Rdg + 5A ±3% Rdg + 5A |
|
A Half Cycle | SR193 &MR193 MN193 5A MN193 100A |
1 to 1200A 5mA to 6A 100mA to 120A |
0.1A 1mA 10mA |
±1% Rdg + 1A ±1% Rdg + 10mA ±1% Rdg + 100mA |
|
Frequency | 40 to 70Hz | 0.01 | ±0.01Hz | ||
Power | |||||
Watts (VA, var) P-Q-S |
Probes: AmpFlex, MiniFlex |
10mW to 10MW 10mW to 10MW |
4 digits min 4 digits min |
±1% Rdg ±1.5% Rdg |
|
Power Factor (Cos Φ/DPF) | -1.000 to 1.000 | 0.001 | ±1° for Φ, +5 cts for cos Φ |
||
Energy | |||||
kWh (kVAh, kvarh) P-Q-S | 1mWh to 9,999,999MWh (MVAh, Mvarh) | ±1% Rdg | |||
Harmonics | DC, 1 to 50 | ||||
Volts & Amp % | f r Absolute V Absolute A THD |
0.0 to 1500% 0.0 to 100% 0.0 to 1000V 0.0 to 1000A 0.0 to 999.9% |
0.1% 0.1% 0.1V 0.1A 0.1% |
±2.5% Rdg + 5cts ±2.5% Rdg + 5cts ±2.5% Rdg + 1V ±2% Rdg + 1A ±2.5% Rdg + 5cts |
|
Phase Angle | -179° to +180° | 1° | ±1.5° +1°x(n/12.5) | ||
Also display Energy loss, Flicker, Plt (2H), Pst (10min), Unbalance V% & A% | |||||
General Features | |||||
Programmable Alarm | Up to 40 types: up to 16,362 recorded max | ||||
Transient Capture | Up to 210 | ||||
Snapshot | Up to 50 (screen BMP + all channels data) | ||||
Interface | Isolated USB, SD card, and Dataview software for real time data, configuration, and reporting included | ||||
Memory | SD card (SDHC compliant, not formatted) standard, for trend Data, Internal memory for In-Rush, transients and alarms | ||||
Display | Color TFT 320 x 240 (1/4 OFT) with graphic representation of system parameters and measurements | ||||
Real-Time Clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture | ||||
Power Supply | External from 110V to 1000V DC to 440Hz | ||||
Charging Time | 6 hours approx. | ||||
Battery Backup | Rechargeable 9.6V NiMH 4000mA battery pack | ||||
Battery Life | ≥10hrs when display ON | ||||
Dimensions (L x W x H) | 10.6 x 9.85 x 7.09” (270 x 250 x 180mm) | ||||
Weight | 8.16 lbs (3.7kg) | ||||
Altitude Operating | 2000m (6560ft) | ||||
Operating Temperature | 32° to 122°F (0° to 50°C) | ||||
Storage Temperature | -4° to 122°F (-20° to 50°C) | ||||
IP Rating | IP67 per IEC 60529 when housing close and A196 sensor used | ||||
Safety | IEC/EN 61010-1 (1000V CAT III-600V CAT IV), IEC 1326-1 |