What’s Included
- ACD-3300 IND
- Test leads
- Type-K thermocouple
- Battery (installed)
- Carrying case
This CAT IV rated ACD-3300 IND Clamp On Tester is ideal for industrial applications and utilities that require an extra level of safety. Including True-rms sensing for accuracy, this clamp on meter’s extra large jaws can clamp on to those wide diameter wires making taking measurements in industrial environments simple.
| FEATURE | ACD-3300 IND | ACDC-3400 IND |
| DC Voltage | 660.0 mV, 6.600 V, 66.00 V, 660.0 V, 1000 V | |
| AC Voltage | 660.0 mV, 6.600 V, 66.00 V, 660.0 V, 750 V | |
| AC Current | 66.00 A, 660.0 A, 1000 A | |
| DC Current | – | 660.0 A, 1000 A |
| Resistance | 660.0 O, 6.600 kO, 66.00 kO, 660.0 kO, 6.600 MO, 66.00 MO | |
| Capacitance | 6.600 nF, 66.00 nF, 660.0 nF, 6.600 µF, 66.00 µF, 660.0 µF, 6.6 mF | |
| Frequency | 66.00 Hz, 660.0 Hz, 6.600 kHz, 66.00 kHz, 660.0 kHz, 1.000 MHz | |
| Continuity | • | |
| Temperature | -30 °F → 1832 °F (-35 °C → 1000 °C) | – |
| Accommodates conductors | up to 2.0″ (51 mm) in diameter | |
| Specifications | |
| DC Volts range | 660.0 mV, 6.600 V, 66.00 V, 660.0 V, 1000 V |
| Accuracy | +/- (0.5% rdg + 2 dgts) |
| Input impedance | 660 mV: >100 MO; 6.6 V:10 MO; 66 V to 1000 V: 9.1 MO |
| Overload protection | 1000 V DC or 750 V AC rms |
| AC Volts True-rms range | 660.0 mV Frequency 50 to 100 Hz, +/- (1.5% rdg + 8 dgts)
6.600 V, 66.00 V Frequency 50 to 500 Hz, +/- (1.5% rdg + 8 dgts) 660.0 V, 750 V Frequency 50 to 500 Hz, +/- (1.5% rdg + 8 dgts) |
| Frequency* (*10% to 100% of voltage range) | 50 to 1 kHz, +/- (0.1% rdg + 5 dgts) |
| Auto power off | Approx. 30 minutes |
| Display | 3″ digit liquid crystal display (LCD) (6600 count) with a 66-segment analog bar-graph |
| Power | Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22 |