・Current up to 1000A rms
・Voltage up to 1000V rms
・Harmonics up to 30th
・Various measurement functions: current, voltage, power, harmonics
and phase detection
・LCD can display simultaneously the values of voltage and frequency
or power and power factor
・Each degree of harmonics can be shown on the LCD of the tester
〇 Measurements of current, voltage, power, harmonics and phase detection are possible.
〇 True RMS: Indicates a correct value at the distorted waveform.
〇 Functions of PEAK, MAX, MIN, AVG are available.
Easy to check the temporal change in the power source.
〇 LCD can display simultaneously the values of voltage and frequency or power and power
factor.
Power measurement on any wiring system is possible.
KEW 2062 can perform Single-phase 2-Wire / Single-phase 3-Wire
and balance and unbalance measurements of Three-phase 3-Wire
/ Three-phase 4 Wire. The double display can simultaneously
show many parameters like W & PF, W & deg, W & VA, W & Var,
V & A, etc.
Various parameters such as |
Total 3-phase power can be
|
By setting the CT and VT ratio and measuring the secondary side of the transformation, the primary side value can be obtained. |
Harmonics of the voltage and current, which cause various failures at the field, can be measured.
It is possible to measure and show each voltage and current harmonics up to 30th.
Total harmonics distortion factor is in two types of THD-R and THD-F. Each degree of harmonics can be
shown on the LCD of the tester. Both the current value (or voltage value) and the content ratio can be displayed on the same screen.
Wiring connections | 1P2W, 1P3W, 3P3W, 3P4W | ||||||
---|---|---|---|---|---|---|---|
Measurements and parameters |
Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Power factor(cosθ), Phase angle, Harmonics(THD-R/THD-F), Phase rotation |
||||||
ACV | |||||||
Range | 1000V | ||||||
Accuracy | ±0.7%rdg±3dgt (40.0 - 70.0Hz) ±3.0%rdg±5dgt (70.1 - 1kHz) |
||||||
Crest factor | 1.7 or less | ||||||
ACA | |||||||
Range | 40.00/400.0/1000A (3 range auto) | ||||||
Accuracy | ±1.0%rdg±3dgt (40.0 - 70.0Hz) ±2.0%rdg±5dgt (70.1 - 1kHz) |
||||||
Crest factor | 3 or less on 40.00A/400.0A range, 3 or less 1500A peak on 1000A range |
||||||
Frequency | |||||||
Display Range | 40.0 - 999.9Hz | ||||||
Accuracy | ±0.3%rdg±3dgt | ||||||
Active power | |||||||
Range | 40.00/400.0/1000kW | ||||||
Accuracy | ±1.7%rdg±5dgt (PF1, sine wave, 45 - 65Hz) | ||||||
Apparent power | |||||||
Range | 40.00/400.0/1000kVA | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Reactive power | |||||||
Range | 40.00/400.0/1000kVar | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Power factor | |||||||
Display Range | -1.000 - 0.000 - +1.000 | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Phase angle (1P2W only) | |||||||
Display Range | -180.0 - 0.0 - +179.9 | ||||||
Accuracy | ±3.0° | ||||||
Harmonics RMS(Content rate) | |||||||
Analysis order | 1st - 30th order | ||||||
Accuracy | ±5.0%rdg ± 10dgt (1 - 10th) ±10%rdg ± 10dgt (11 - 20th) ±20%rdg ± 10dgt (21 - 30th) |
||||||
Total harmonics THD-R/THD-F | |||||||
Display Range | 0.0% - 100.0% | ||||||
Accuracy | ±1dgt against the calculated results of each measured value | ||||||
Phase rotation | ACV 80 - 1100V (45 - 65Hz) | ||||||
Other functions | MAX/MIN/AVG/PEAK, Data hold, Back light, Auto power off | ||||||
General | |||||||
Power source | LR6(AAA)(1.5V) ×2 | ||||||
Continuous measuring time |
Approx. 58 hours | ||||||
Conductor size | φ55mm max. | ||||||
Dimensions / Weight | 247(L) × 105(W) × 49(D) mm / Approx.490g(including batteries) | ||||||
Applicable Standards | IEC 61010-1, IEC 61010-2-032, IEC 61326-1,-2-2 (EMC), IEC 60529 (IP40) CAT IV 300V / CAT lll 600V / CAT ll 1000V Pollution degree 2 |
||||||
Accessories | 7290 (Voltage test lead set) 9198 (Carrying case) LR6(AAA)×2, Instruction Manual |