021 -2216 3350
info@bapj.co.id

Detcon MicroSafe 500 & 600 Series Intelligent Fixed Gas Detectors

Update Terakhir
14 OKTOBER 2025
Negara Asal
UNITED STATES
Pembelian minimum
1
Harga
NEGO
Minta Penawaran
Sharing:

Deskripsi produk

Detcon MicroSafe 500 & 600 Series Intelligent Fixed Gas Detectors

 

Detcon MicroSafe 500 & 600 Series Intelligent Fixed Gas Detectors

The Detcon MicroSafe 500 and 600 Series gas detectors feature a non-intrusive operator interface. Calibration and programming instructions appear in simple intuitive and sequential script on a 16-character backlit display. The transmitter design incorporates extensive fault diagnostics with each condition conveniently identified on the transmitter display.

The 500 Series comes standard with a linear 4-20 mA output, one-man remote calibration, self-adjusting zero and span, and LED indicators for fault and calibration status.

The 600 Series includes the same features as the 500 with the addition of 3 alarm relays and an RS-485 serial communications port.

Electrical Classification - Explosion proof

System Specifications
Sensor Type Matched-pair catalytic bead
Sensor Life 3 to 5 years typical
Measurement Range 0-100% LEL (lower explosive limit)
Accuracy/Repeatability ±3% 0-50% LEL
±5% 50-100% LEL
Response/Clearing Time T50 <10 seconds; T90 <30 seconds
Zero Drift <5% per year
Outputs Linear 4-20 mA DC
HART (optional)
Electrical Classification Explosion proof
CSAus
Class I, Division 1, Groups C, D (Tamb = -25°C to +40°C)
Class I, Zone 1, Group IIB
cCSA
Class I, Division 1, Groups C, D (Tamb = -40°C to +40°C)
Class I, Zone 1, Group IIB
Performance Approvals CSA C22.2 #152-M1984, ISA 12.13.01-2003
Safety Approvals cCSAus
Ingress Protection NEMA 4X, IP66
Warranty Sensor: 2 year warranty
Transmitter: 2 year warranty
Operating Temperature Range -40°C to +40°C; -40°F to 104°F (CANADA)
-25°C to +40°C; -13°F to 104°F (USA)
Storage Temperature Range -40°C to +75°C; -40°F to +167°F
Operating Humidity Range 5-100% RH non-condensing
Operating Pressure Range Atmospheric ±10%
Dimensions 10”H (including splashguard) x 6.1”W x 4.3”D
254mmH x 155mmW x 109mmD
Mounting holes (J-box) 5.5”; 140mm center to center
Weight 6 lbs; 2.72kg (w/aluminum j-box)
9 lbs; 4.08kg (w/stainless steel j-box)
Power Input 12-28 VDC
Power Consumption Normal operation = 68mA (<1.7 watt)
Maximum = 87mA (2 watts)
RFI/EMI Protection Complies with ISO 92.0.01
Analog Output Linear 4-20mA DC (1,000 ohms max loop load @ 24VDC)
0mA All Fault Diagnostics
2mA In-Calibration
4-20mA 0-100% full-scale
22mA Over-range condition
Status Indicators 4-digital LED display with gas concentration
Full-script menu prompts for AutoSpan, Set-up Options, and Fault Reporting
4 LEDs for Alarm 1, Alarm 2, Fault, and Calibration
Faults Monitored Loop, Input Voltage, Zero Sensor, Processor, Memory, Calibration
Cable Requirements Power/Analog 3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
I/O Protection Over-voltage, Miswiring, EMI/RFI Immunity

'

'

'

Catatan:

 

Harap Tanya stok sebelum melakukan pemesanan.

Barang akan dipacking dengan aman dan rapi.

Tidak ada complain yang diterima setelah transaksi selesai.

Tanpan video unboxing, komplain tidak akan diproses.

Terima kasih!

 

 

Produk Terkait

                                                                                      PT. Bopana Arga Prima Jaya

Office

Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16 Bekasi Utara 17122 , Bekasi
Bekasi , Indonesia

Contact
021 -2216 3350
info@bapj.co.id
Share
apartmentenvelopebookmarkcarttagphone-handsetearthhistorymagnifiercross
× How can I help you?