021 -2216 3350
info@bapj.co.id

Earth Tester PCE-ITE 50

Update Terakhir
Negara Asal
GERMANY
Pembelian minimum
1
Harga
Nego
Kategori
Minta Penawaran
Sharing:

Deskripsi produk

DESCRIPTION

Earth Tester / Electrical resistance / Earthing resistance /  
Loop impedance / Voltage measurement /  Low resistance measurement / RCD test

The earth tester is a robust earth tester with a large 3.5" TFT color LCD display. The earth tester also offers, in addition to the various measuring modes such as insulation resistance, grounding resistance, loop impedance, voltage, low-impedance measurement and RCD test with the camera function, the possibility of documenting suitable photos with the measurements. With the earth tester, you can ensure that fixed installations are safely and correctly installed. Thanks to the dual display, the intuitive symbols and the high viewing angle, you can comfortably and quickly perform your measurements with the earth tester. With the low-resistance measurement of the earth tester, you can check grounding conductors, potential equalization rails and protective conductors for low impedance.

The measuring range for low-resistance measurement with the earth tester is in the range of 0 - 2000 Ω with a resolution of 0.001 - 1 Ω.  Probably the most important measurement of the earth tester is the measurement of insulation resistance. Electrical cables are placed under voltage during the insulation measurement in order to detect fault currents, Which generate material migration or heat. In most cases, these current faults are so minimal that they are not detected by protective devices and in the worst case they can lead to a fire. The earth tester can carry out installation measurement with a test voltage of 125V, 250V, 500V or 1000V. The load current is in each case 1 mA. The earth tester is independent of the mains supply. In order to bring all systems and circuits of a power supply system to a common potential (ground reference or potential reference) and to protect against short-circuit currents and overvoltages, the earthing resistor should be as low-impedance as possible. With a measuring range of 0 ... 2000 Ω with a resolution of 0.01 ... 1 Ω, the earth tester offers all the prerequisites for a meaningful measurement of the grounding resistance.

HIGHLIGHTS

- 3.5" color TFT LCD display
- Loop resistance L-N, L-PE and N-PE
- Adjustable FI test current
- SD card and Bluetooth
- Dual display
- Good / bad FI test
- Low Ohm measurement
- Up to 1000V terminal voltage

SPECIFICATION

Isolation test
Terminal voltage Measuring range Resolution Accuracy Load current Short circuit current
125V (0 ... 10 %) 0,125 ... 4 MΩ 0.001 MΩ ± (2% + 10 digits) 1-mA @ Last 125 kΩ <= 1-mA
4,001 ... 40 MΩ 0.01 MΩ ± (2% + 10 digits)
40,01 ... 400 MΩ 0.1 MΩ ± (4% + 5 digits)
400,1 ... 1000 MΩ 1 MΩ ± (5% + 5 digits)
250V (0 ... 10 %) 0,125 ... 4 MΩ 0.001 MΩ ± (2% + 10 digits) 1-mA @ Last 250 kΩ <= 1-mA
4,001 ... 40 MΩ 0.01 MΩ ± (2% + 10 digits)
40,01 ... 400 MΩ 0.1 MΩ ± (3% + 2 digits)
400,1 ... 1000 MΩ 1 MΩ ± (3% + 2 digits)
500V (0 ... 10 %) 0,125 ... 4 MΩ 0.001 MΩ ± (2% + 10 digits) 1-mA @ Last 500 kΩ <= 1-mA
4,001 ... 40 MΩ 0.01 MΩ ± (2% + 10 digits)
40,01 ... 400 MΩ 0.1 MΩ ± (3% + 2 digits)
400,1 ... 1000 MΩ 1 MΩ ± (4% + 5 digits)
1000 V (0 ... 10 %) 0,125 ... 4 MΩ 0.001 MΩ ± (3% + 10 digits) 1-mA @ Last 1 MΩ  <= 1-mA
4,001 ... 40 MΩ 0.01 MΩ ± (2% + 10 digits)
40,01 ... 400 MΩ 0.1 MΩ ± (3% + 2 digits)
400,1 ... 1000 MΩ 1 MΩ ± (4% + 5 digits)
Low Ohm 
Measuring range Resolution Accuracy Max. open circuit voltage Overload protection
2,000 Ω 0.001 Ω ± (1.5% + 30 digits) 5.8V 250 Vrms
20,00 Ω 0.01 Ω ± (1.5% + 3 digits) 5.8V 250 Vrms
200,0 Ω 0.1 Ω ± (1.5% + 3 digits) 5.8V 250 Vrms
2000 Ω 1 Ω ± (1.5% + 5 digits) 5.8V 250 Vrms
Continuity tester
Measuring range Resolution Max. open circuit voltage Overload protection Short circuit current
2000 Ω 0.01 Ω 5.8V 250 Vrms >= 200-mA
Grinding resistance
L-PE (Hi-Amp): Load current 4.0 A
Measuring range Resolution Accuracy
0.23 ... 9.99 Ω 0.01 Ω ± (4% + 4 digits)
10.0 ... 99.9 Ω 0.1 Ω ± (4% + 4 digits)
100 ... 999 Ω 1 Ω ± (4% + 4 digits)
L-PE (without tripping): Load current 15-mA
Measuring range Resolution Accuracy
0.23 ... 9.99 Ω 0.01 Ω ± (5% + 6 digits)
10.0 ... 99.9 Ω 0.1 Ω ± (5% + 6 digits)
100 ... 999 Ω 1 Ω ± (5% + 6 digits)
L-N: Load current 4.0 A
Measuring range Resolution Accuracy
0.23 ... 9.99 Ω 0.01 Ω ± (4% + 4 digits)
10.0 ... 99.9 Ω 0.1 Ω ± (4% + 4 digits)
100 ... 999 Ω 1 Ω ± (4% + 4 digits)
RCD Test
RCD (In) 10-mA, 30-mA, 100-mA, 300-mA, 650-mA, 1 A
Factors x 1/2, x1, x2, x5
Accuracy of the tripping time ± (1% + 1 ms)
Signal form of the test current Sine (AC)
Tripping characteristics G and S
Release time 0° or 180°
Voltage range 194 ... 260V AC (50/60 Hz)
Accuracy of current measurement ± (5% + 2 digits)
RCD Types Type A, Type B
Voltage measurement
Measuring range Resolution Accuracy
80...500 V AC/DC 1 V ± (2 % + 2 digits)
Frequency measurement
Measuring range Resolution Accuracy
45...65 Hz 1 Hz ±2 Hz
Grounding measurement
Measuring range Resolution Accuracy
0.00...99.99 Ω 0.01 Ω ± (2% + 30 digits)
100.0...999.9 Ω 0.1 Ω ± (2% + 6 digits)
1000...2000 Ω 1 Ω ± (2% + 6 digits)
General specifications
Power supply 8 x 1.2 ... 1.5V AA batteries
Operating time ca. 15 h
Measurement category CAT III 600V
Protection class IP 65
Display 3.5" TFT (320 x 240 Pixel)
Operating environment 0 ... 45°C
0 ... 95% rH, non condensing
Measurements 24.2 x 10.5 x 14.5 cm
Weight 1.56 kg / 3.4 lbs

DELIVERY SCOPE

1 x Earth Tester PCE-ITE 50
1 x User manual

Produk Terkait

                                                                                      PT. Bopana Arga Prima Jaya

Office

Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16 Bekasi Utara 17122 , Bekasi
Bekasi , Indonesia

Contact
021 -2216 3350
info@bapj.co.id
Share
apartmentenvelopebookmarkcarttagphone-handsetearthhistorymagnifiercross
× How can I help you?