021 -2216 3350
info@bapj.co.id

Fluke 355 True RMS 2000 A Clamp Meter

Update Terakhir
Fluke 355 True RMS 2000 A Clamp Meter
Negara Asal
AMERIKA
Pembelian minimum
1
Harga
Kategori
Minta Penawaran
Sharing:

Deskripsi produk

Key features

  • Reliably handle a wide range of high-current applications with 2000 A AC + DC True RMS, 1400 A AC, and 2000 A DC
  • The large 58 mm (2.3 in) jaw capacity is suitable for large or multiple conductors
  • CAT IV 600 V, CAT III 1000 V rating for added user protection
  • In-rush current measurement captures ‘power-on’ surge current with accuracy and repeatability

Product overview: Fluke 355 True RMS 2000 A Clamp Meter

Versatile and rugged clamp meter for high currents

Confidently take reliable readings with the True RMS Fluke 355 digital clamp meter, the tool of choice for high current clamp-on amp meter measurement up to 2000 A. The extra-wide jaw easily clamps around large conductors, typically found in high-current applications. The extra rugged design and CAT IV 600 V, CAT III 1000 V ratings add an extra element of user protection when taking high-powered measurements.

Accurate peak measurements can be taken using the in-rush current mode, ideal for motors and inductive loads. The 355 also measures voltage and resistance, making this an ideal clamp meter for utilities, electrical contractors and industrial service technicians.

Easy to use all-in-one tool

  • High voltage measurement of 1000 V AC + DC True RMS, 600 V AC, and 1000 V DC allows the user to perform multiple tests with only one tool
  • Resistance to 400K ohms coupled with a continuity beeper provide the convenience of a multimeter in a clamp meter
  • Accurately measure frequency up to 1 kHz for optimum troubleshooting
  • Quickly analyze readings using the MIN, MAX, and AVG functions
  • A large backlit display allows for easy visibility in low-lit areas
  • Use the display hold feature to capture readings even when the display cannot be viewed
  • Use the low-pass filter to smooth out noisy loads and stabilize readings

What's in the box:

  • 355 2000 A Clamp Meter
  • (1 pair) TL224 1.5 m silicone rubber test leads
  • (1 pair) TP2 test probes
  • (1 pair) AC285 alligator clips
  • 6 AA batteries (Installed)
  • C43 soft carrying case
  • Quick Reference Guide

Specifications: Fluke 355 True RMS 2000 A Clamp Meter

Electrical Specifications
Current measurement DC and AC 10 Hz to 100 Hz Range 40 A / 400 A / 2000 A / 1400 AC rms
Resolution 10 mA / 100 mA / 1 A
Accuracy A: 1.5% rdg + 15 digits
A: 1.5% rdg + 5 digits
Trigger level for Inrush 0.50 A / 5.0 A / 5 A
Trigger level for Hz filter OFF 2.50 A / 2.5 A / 8 A
Trigger level for Hz filter ON 0.50 A / 2.5 A / 8 A
Crest Factor (50/60 Hz) Range 40 A / 400 A / 2000 A / 1400 AC rms
Crest Factor1 2 @ 33 A, 2.4 @ 27 A
2 @ 330 A, 2.4 @ 270 A
2 @ 1000 A, 2.4 @ 833 A
Current measurement AC 100.1 Hz to 1 kHz Range 40 A / 400 A / 2000 A; 1400 AC rms
Resolution 10 mA / 100 mA / 1 A
Accuracy 10 A: 3.5% rdg + 15 digits
10 A: 3.5% rdg + 5 digits
Trigger level for Inrush 0.50 A / 5.0 A / 5 A
Trigger level for Hz filter OFF 2.50 A / 2.5 A / 8 A
Trigger level for Hz filter ON 0.50 A / 2.5 A / 8 A
Voltage measurement DC and AC 10 Hz to 100 Hz
(600 V and 1000 V ranges have 10% over range to 660 V and 1100 V respectively.)
Range 4 V / 40 V / 400 V / 600 V AC rms / 1000 VDC
Resolution 1 mV / 10 mV / 100 mV / 1 V
Accuracy 1% rdg + 10 digits
1% rdg + 5 digits
Trigger level for Hz filter OFF 0.25 V / 6 V
Trigger level for Hz filter ON 0.25 V / 6 V
Voltage measurement AC 100.1 Hz to 1 kHz
(600 V and 1000 V ranges have 10% over range to 660 V and 1100 V respectively.)
Range 4 V / 40 V / 400 V / 600 V ac rms
Resolution 1 mV / 10 mV / 100 mV / 1 V
Accuracy 3% rdg + 10 digits
3% rdg + 5 digits
Trigger level for Hz filter OFF 0.050 V / 0.25 V / 6 V
Trigger level for Hz filter ON 0.050 V / 0.25 V / 6 V
Ohms measurement Range 4 kΩ / 40 kΩ / 400 kΩ
Resolution 0.1 Ω / 1 Ω / 10 Ω / 100 Ω
Accuracy 1.5% + 5 digits
Continuity beeper On at ≤ 30 Ω
Off at ≥ 100 Ω
Frequency measurement Measurement range 5.0 Hz to 1 kHz
Resolution 0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz)
Accuracy – 5.0 Hz to 100 Hz 0.2% + 2 counts
Accuracy – 100.1 Hz to 1 kHz 0.5% + 5 counts
Trigger level Refer to current and voltage tables
1. Add 2% to error spec for CF > 2
General Specifications
Batteries Six 1.5 V AA NEDA 15 A or IEC LR6
Battery life (with typical usage, backlight off) 100 hours
Test leads Rated to 1000 V
Weight .814 kg (1.8 lb)
Jaw size 58 mm (2.28 in)
Dimensions (L x W x D) 300 x 98 x 52 mm (12 x 3.75 x 2 in)
Safety rating IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III
Environmental Specifications
Operating temperature 32°F to +122°F (0°C to +50°C)
Storage temperature -4°F to 140°F (-20°C to +60°C)
Operating humidity 0 to 95% (non-condensing)
Operating altitude 2000 m
Storage altitude 10,000 m
IP rating 42 (indoor use only)
Drop test requirements 1 m
EMI, RFI, EMC FCC part 15, IEC/EN 61326-1:1997 class B
IEC/EN 61326:1997 3 V/m, performance criteria B, EN61325
Temperature coefficients Current 0.1% of reading per °C outside 22°C to 24°C
Voltage 0.1% of reading per °C outside 22°C to 24°C