021 -2216 3350
info@bapj.co.id

Honeywell SS4 UV and UV/IR Flame Detector

Update Terakhir
1 DESEMBER 2025
Negara Asal
UNITED STATES
Pembelian minimum
1
Harga
NEGO
Kategori
Minta Penawaran
Sharing:

Deskripsi produk

Honeywell SS4 UV and UV/IR Flame Detector

Product Features

  • Electro-optical digital detectors represent leading-edge UV and UV/IR technology.
  • Detects hydrocarbon and non-hydrocarbon-based fires
  • Built-in test for optical “through the lens” testing
  • False alarm immunity

The Honeywell SS4 UV and UV/IR Flame Detector represents the world’s pre-eminent UV/IR technology for Electro-Optical Flame Detectors with tens of thousands successfully operating in a multitude of installations worldwide. This multi-spectrum detector senses radiant energy in the ultraviolet (UV), visible and Wide Band Infrared™ (IR) spectrum. The radiant energy from all flaming fires will alert the detector to their presence.

    • To eliminate common nuisance false alarms that occasionally occur with UV-only, IR-only, Dual IR or Dual Mode UV/IR detectors, the SS4 Flame Detectors’ FireLogic signal processing requires that UV, visible and Wide Band IR radiant energy all be evaluated before declaring a fire. The smart detector utilises real-time signal processing algorithms that are optimised to alarm on all types of fires, while virtually eliminating the possibility of false alarms.

Honeywell Analytics SS4-AS:

        • The Honeywell SS4-AS processes UV, IR and Visible (VIS) spectral ranges from ruggedized solar-blind UV, “Quantum-Effect” IR and VIS sensors correspondingly. It is optimised for the detection of hydrogen, ethanol, methanol and methane (natural gas) fires and like the other detectors in its family, it responds to Type A, B and C flaming fires.

Honeywell Analytics SS4-AUV:

            • The Honeywell SS4-AUV represents the leading-edge technology of UV optical flame detectors. This flame detector senses radiant energy in the ultraviolet (UV) spectrum. The radiant emissions of flaming fires will alert the detector to their presence.

Honeywell Analytics SS4-A and SS4-AS Features:

▪ Multi-Spectrum™: senses ultraviolet, visible and Wide Band Infrared™

▪ Built-in test for optical “through the lens” testing

▪ False alarm immunity

▪ Detects hydrocarbon and non-hydrocarbon-based fires

▪ Wide field-of-view and solar-blind

▪ Adjustable detector sensitivity

▪ Microprocessor based algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™

▪ Wide temperature range of operatio

▪ Compatible with standard approved fire alarm panels

▪ Explosion-proof housing

▪ Time programmable alarm verification

Honeywell Analytics SS4-AUV Features:

▪ Senses solar-blink ultraviolet band

▪ Built-in test for optical “through the lens” testing

▪ Utilises long-life, ruggedised UV sensors

▪ Detects hydrocarbon and non-hydrocarbon-based fires

▪ Wide field-of-view and solar-blind

▪ Adjustable detector sensitivity

▪ Microcomputer based algorithms: FirePic™, Snapshot™ and UV Plot

▪ Wide temperature range of operation

▪ Compatible with standard approved fire alarm panels

▪ Explosion-proof housing

▪ Time programmable alarm verification

Applications include:

▪ Petrochemical facilities and Refineries

▪ Co-Generation plants

▪ Aircraft hangars

▪ Silane and Hydrogen gas storage

▪ Gas Turbines and power plants

▪ Gas compressor stations

▪ Warehouses

▪ Semiconductor

 

Product Specification

General
Sensitivity Adjustable between 18 m (60 ft.), 14 m (45 ft.), 9 m (30 ft,) and 4.5 m (15 ft.) to a 0.1 m2 (1 sq. ft.) gasoline fire
Response time 2-5 seconds to 0.1 m2 (1 sq. ft.) of gasoline fire at 18 m (60 ft.)
Field-of-view 120 degrees cone of vision (60 degrees from on axis).
Spectral Sensitivity - Ultraviolet: 185 to 260 nanometres
- Wide Band Infrared: 0.7 to 3.5 micrometres (SS4-A and SS4-AS only)
- Visible: 400 to 700 nanometres (SS4-A and SS4-AS only)
Input power 24 Vdc nominal (20.5 to 34 Vdc)
Power Consumption - 68 mA normal operation (relay version)
- 75 mA alarm condition (relay version)
- 95 mA alarm condition (analog version)
Output relays
Fire alarm relay
Fire verify relay
Fault relay
- NO & NC contacts, Latching / Non-Latching, switch selectable
- NO & NC contacts, Adjustable time from 0 to 30 seconds
- NO & NC contacts, Relay contact ratings: 0.5 A at 120 Vac, 1.0 A at 24 Vdc, non-inductive, Fault relay is energised during normal operation, All other relays are de-energised
Operating temperature -40ºC to 85ºC (-40ºF to +185ºF)
Humidity range 10 to 98% RH, non-condensing
Weight - 1.8 kg (4 pounds) - Aluminum
- 3.4 kg (7.5 pounds) - Stainless Steel
Housing Copper-free aluminum (less than 0.4%) powder coated NEMA4 (IP66), tamper resistant with integral dual 3/4” NPT conduit openings or optional M25. Stainless steel housing available
Certification - FM
- Class I, Div. 1 & 2, Groups B, C and D
- Class II, Div. 1 & 2, Groups E, F and G
- Class III
- ATEX, IECEX II 2 GD: Gas: Ex d IIC T4(Ta: -40°C to + 110 °C), T5 (Ta: -40°C to + 75°C), T6 (Ta: -40°C to +60°C)) Gb, Dust: Ex tb IIIC IP66 T 135°C Db
- CE
- FMEDA meets IEC 61508 safety requirements
Vibration Meets or exceeds MIL Spec 810 C Method 514.2, Curve AW
Mounting Swivel bracket assembly
Warranty Three years from date of shipping
Output Option mA 0-20 mA ‘source’

'

'

'

Catatan:

 

Harap Tanya stok sebelum melakukan pemesanan.

Barang akan dipacking dengan aman dan rapi.

Tidak ada complain yang diterima setelah transaksi selesai.

Tanpan video unboxing, komplain tidak akan diproses.

Terima kasih!

 

 

Produk Terkait

                                                                                      PT. Bopana Arga Prima Jaya

Office

Jl. Jupiter VI, Perum Bintang Metropol Blok A7 No.16 Bekasi Utara 17122 , Bekasi
Bekasi , Indonesia

Contact
021 -2216 3350
info@bapj.co.id
Share
apartmentenvelopebookmarkcarttagphone-handsetearthhistorymagnifiercross
× How can I help you?