The IoT meter has an adjustable measuring range of 0… 600 V AC/DC and can therefore measure a wide variety of voltages. For example, it is possible to connect the IoT meter to the supply line in order to monitor the applied voltage. In addition to voltage measurement, the IoT meter can also measure the current directly with a maximum adjustable measuring range of 0 … 5 A AC/DC. A current transformer can be connected to the IoT meter to expand the current range. The measured value is then converted by the IoT meter into a standardized analog 4 … 20 mA or 0 … 10 V signal. Thus the IoT meter is the ideal extension of a process control.
Since the input and output range can be set identically, the transmitter can be used for galvanic decoupling. The transmitter is configured directly via the keypad. This means that no additional cable or software is required for the settings of the signal converter. The transmitter is mounted on a DIN rail. The transmitter is operated with a voltage of 18 … 265 V AC/DC at a frequency of 45 … 65 Hz.
Input signals | |
AC voltage | |
Adjustable measuring ranges | 0 ... 1 / 2 / 10 / 15 / 30 / 60 / 100 / |
150 / 300 / 450 / 600 V AC, | |
0 ... 50 / 60 / 75 / 100 / 150 / | |
200 / 300 / 500 mV AC | |
Accuracy | <0.3 % of full range |
Maximum input signal | 800 V AC for the measuring ranges 10 ... 600 V AC, |
50 V AC for the measuring ranges 50 mV AC ... 2 V AC | |
Measuring resistance | 13 MΩ for the measuring ranges 10 ... 600 V AC, |
81 KΩ for the measuring ranges 50 mV AC ... 2 V AC | |
Measurement type | True RMS |
Protection category | CAT-II 300 V AC |
DC voltage | |
Adjustable measuring ranges unipolar | 0 ... 1 / 2 / 10 / 15 / 30 / 60 / 100 / |
150 / 300 / 450 / 600 V DC, | |
0 ... 50 / 60 / 75 / 100 / 150 / | |
200 / 300 / 500 mV DC | |
Adjustable measuring ranges bipolar | ±1 / ±2 / ±10 / ±15 / ±30 / ±60 / ±100 |
/ ±150 / ±300 / ±450 / ±600 V DC, | |
±50 /± 60 / ±75 / ±100 / ±150 / | |
±200 / ±300 / ±500 mV DC | |
Accuracy | <0.2 % of full range |
Maximum input signal | 800 V DC for the measuring ranges 10 ... 600 V DC, |
50 V DC for the measuring ranges 50 mV DC ... 2 V DC | |
Measuring resistance | 13 MΩ for the measuring ranges 10 ... 600 V DC, |
81 KΩ for the measuring ranges 50 mV DC ... 2 V DC | |
Alternating current | |
Adjustable measuring ranges | 0 ... 1 / 2 / 3 / 4 / 5 A AC, |
0 ... 5 / 10 / 20 / 50 / 75 / 300 / 500 mA AC | |
Accuracy | <0.3 % of full range |
Maximum input signal | 7 A AC for the measuring ranges |
300 mA AC ... 5 A AC (for a maximum of 7 seconds), | |
150 mA AC for the measuring ranges | |
5 mA AC ... 75 mA AC | |
Measuring resistance | 20 mΩ for the measuring ranges 300 mA AC ... 5 A AC, |
3.33 Ω for the measuring ranges 5 mA AC ... 75 mA AC | |
Direct current | |
Adjustable measuring ranges | 0 ... 1 / 2 / 3 / 4 / 5 A DC, |
0 ... 5 / 10 / 20 / 50 / 75 / 300 / 500 mA DC | |
Accuracy | <0.2 % of full range |
Maximum input signal | 7 A DC for the measuring ranges |
300 mA DC ... 5 A D (for a maximum of 7 seconds), | |
150 mA DC for the measuring ranges | |
5 mA DC ... 75 mA DC | |
Measuring resistance | 20 mΩ for the measuring ranges 300 mA DC ... 5 A DC, |
3.33 Ω for the measuring ranges 5 mA DC ... 75 mA DC | |
Frequency | |
Adjustable measuring ranges for voltage | 0 ... 100 / 45 ... 55 / 55 ... 65 Hz |
Adjustable measuring ranges for current | 0 ... 100 / 45 ... 55 / 55 ... 65 Hz |
Accuracy | <0.2 % of full range |
Reaction time | |
AC signals | <350 ms typically 0 ... 99 % |
DC signals | <90 ms typically 0 ... 99 % without filter |
<175 ms typically 0 ... 99 % with 50/60 Hz filter | |
<350 ms typically 0 ... 99 % with 50/60 Hz filter | |
Output signals | |
Active current output | 4 ... 20 mA minimum 0 mA and maximum <22 mA |
Passive current output | 4 ... 20 mA maximum 30 V DC |
Voltage output | 0 ... 10 V DC |
minimum 0 V DC and maximum <11 V DC | |
Load resistance | current output maximum <400 Ω |
voltage output minimum >1 KΩ | |
Further specifications | |
All accuracies relate to an ambient temperature of 25 °C / 77 °F | |
Thermal drift | 150 ppm / °C |
Power supply | 18 ... 265 V AC/DC isolated |
( 20 ... 240 V AC/DC ±10 %) | |
Frequency | 45 ... 65 Hz |
Power consumption | <1.5 W |
Conductor cross-section | 1 ... 2.5 mm² |
Overvoltage category | CAT-II |
Isolation | 3000 Vrms for 60 seconds |
Protection class | IP30 |
Impact protection | IK06 |
Operating conditions | 0 ... 50 °C / 32 ... 122 °F, 0 ... 95 % RH, non-condensing |
Storage conditions | -20 ... 70 °C / -4 ... 158 °F, 0 ... 95 % RH, non-condensing |
Warm-up time | 15 minutes |
Maximum working height | 2000 meters / 6561 feet |
Mounting | standard DIN rail 35 x 7.5 mm / 1.3 x 0.3" |
Connection | plug-in screw terminal (grid 5.08 mm / 0.2") |
Housing material | polyamide V0 |
Dimensions | 106 x 108 x 22.5 mm / 4.1 x 4.2 x 0.9" |
Weight | <150 g / 5.3 oz |